3/3/2024 0 Comments Rslogix project migrator sy5![]() Step 7) Then we select the CSV tab, and click on OK: Step 6) This is done in RSLogix 500 by selecting Tools, then Database, then ASCII Export: Step 5) Back in the Project Migrator, we can see the next step is to export our comments and symbols: Step 4) After we select save, we can click on OK to select the default export mode: Step 3) According to the above instructions, we first need to open our SLC-500 program in RSLogix 500 and save it as an. In today’s example we’ll choose the SLC-500 option: Step 2) Here we can select either a PLC-5 or SLC-500/MicroLogix project. Step 1) When you install Studio 5000 the RSLogix Project Migrator is also installed, and the first step it to launch it: ![]() UPDATE – November 2021 by SMT: Rockwell no longer makers the Translation Tool or Project Migrator available as a download, so if you don’t have either in your RSLogix/Studio 5000 installation files or discs, you can try the “new” feature in RSLogix500 v12 and RSLogix5 v10 which allows you to save your program as a Logix file by using the “save as type” menu option, and choosing “Logix Designer Files (*.ACD)” For more information see the free tech note below: Note: To get RSLogix Project Migrator version 3.0, search the below website for “ RSLogix Project Migrator (it also comes with RSLogix/Studio 5000 v19 and up)” In this article we will convert SLC-500 programs to ControlLogix using the RSLogix Project Migrator version 3.0.